You are here: Driver Reference > DNP3 Driver > Scanning for Data on DNP3 Devices > Level 3 Scan

Level 3 Scan

ATTENTION: If you configure a point in the outstation to generate DNP3 events (see DNP3 Integrity and Data Classes), it is not advisable to perform DNP3 Level 3 Scans for that point. (The DNP3 standard dictates that event data for a DNP3 point has to be transmitted in chronological order. As a DNP3 Level 3 Scan returns a point’s current value without any preceding DNP3 event data, the value of the point may be returned out-of-order.)

If point data is not retrieved from a DNP3 outstation by other means, such as an Integrity Poll, you can retrieve that data using the Perform Level 3 Scan pick action.

In order to retrieve Class 0 static (current value) data in this way, you need to:

For more information on either of the above, see Configure General Point Properties.

ClearSCADA retrieves any DNP3 Status Point data by performing a Level 3 scan.

Level 3 Scans do not apply to DNP3 Pulse Actions.

(With points that are assigned a Scan Group (Confidence Interval) but are excluded from Level 3 Scans, the DNP3 driver does not schedule a poll of the outstation when the Scan Group timer expires. Instead, it updates the point’s value with the response to the next scheduled Integrity Poll.)