You are here: Driver Reference > IEC 60870-5 Slave Driver > IEC 60870-5 SLAVE Driver Guide - Configuring an IEC 60870-5 Slave Outstation

Configuring an IEC 60870-5 Slave Outstation

This section covers the configuration of IEC 60870-5 Slave outstations—outstations that allow ClearSCADA to operate as an IEC 60870-5 Controlled Station (outstation). When ClearSCADA is configured as an IEC 60870-5 slave, it appears as a Controlled Station to an IEC 60870-5 Controlling Station (SCADA master station).

The SCADA master station accesses the data in the ClearSCADA database by communicating with one or more of the following ClearSCADA database items:

You configure each outstation’s properties using the fields on the IEC 60870-5 Slave Direct Outstation Form, or the IEC 60870-5 Slave Logical Outstation Form, as appropriate.

Each Form has several tabs.

Use the Value Maps tab to:

Use the IEC 60870-5 tab to:

On an IEC 60870-5 Slave Direct Outstation that communicates using the IEC 60870-5-101 protocol, also use the IEC 60870-5 tab to:

On an IEC 60870-5 Slave Direct Outstation that communicates using the IEC 60870-5-104 protocol, use the Network tab to specify the Host Address and Port (see Define an Outstation’s Network Properties in the ClearSCADA Guide to Advanced Drivers). (Port number 2404 is the TCP and UDP port that is registered for IEC 60870-5-104 use with the IANA (Internet Assigned Numbers Authority).)

On an IEC 60870-5 Slave Logical Outstation, use the Remote tab to:

The fields on other tabs are common to outstations on many advanced drivers—for information, see Tabs on Outstation Forms in the ClearSCADA Guide to Advanced Drivers.


ClearSCADA 2015 R2