You are here: Driver Reference > OPC - Simple Driver > Configuring Digital Points > Prevent Fleeting Changes in Value from Changing the Point State

Prevent Fleeting Changes in Value from Changing the Point State

Use the Persistence field near the top of the OPC tab to prevent a change in value from affecting the point state until the point has been in that state for a specified time. This allows the driver to ignore fleeting changes in point value, and prevents ClearSCADA raising change of state alarms and logging change of state events when a point value is fluctuating.

When the point changes value, any change of point state is delayed until the point remains in the new state for a specified amount of time. If the point does not remain in the new state for the required amount of time, no change in point state is recorded.



ClearSCADA 2015 R2