You are here: Driver Reference > DNP3 WITS Driver > DNP3 WITS Driver Guide - Configuring a WITS Pulse Action

Configuring a WITS Pulse Action

You use a pulse action to send an electrical pulse, for a defined period of time, to a point connected to a control device. For example, to start a motor or to instruct a pump to start running. A pulse is a pulsed (rather than a maintained) binary output control.

 

The ClearSCADA WITS driver supports the following types of pulse action:

 

To configure a pulse action you use either the WITS Pulse (NULL) Form or the WITS Pulse (Trip-Close) Form as appropriate. Each Form contains a number of fields, organized into tabs. Use the fields to enter the pulse action properties.

Some of the tabs are common to many types of database item. For more information on the Identification, User Methods, Alarm and Redirection tabs, see Tabs on Point Forms in the ClearSCADA Guide to Advanced Drivers.

 

You use the Pulse Action tab on each Form to:

 

You use the Pulse (NULL) tab on the WITS Pulse (NULL) Form to Configure a WITS Pulse (NULL) Action.

You use the Pulse (Trip Close) tab on the WITS Pulse (Trip-Close) Form to Configure a WITS Pulse (Trip-Close) Action.


ClearSCADA 2015 R2