Off Scan (WITS Point)
Associated with: WITS Database Points
Security permission required to access this pick action: Off/On Scan
NOTE: The ability to place points and outstations Off Scan is disabled on most systems by default. (Its permission is typically denied on a per server basis.)
UNEXPECTED BEHAVIOR OF APPLICATION
You can use the Off Scan action to set a point that is currently 'on scan' to 'off scan'. When a point is 'off scan':
- The Field Device does not log data or generate events for the point
- The point's ONLINE object flag clears and any action for the ONLINE flag is performed (see DNP3 Object Flag Actions).
- Configuration changes to the point can still be applied.
- Output points cannot be controlled (the Field Device will reject any control).
You would use the Off Scan action on a point when you want to stop a point's data from being reported. For example, if an instrument develops a fault, an operator may put the point for the instrument to 'off scan' (as this will suppress the data being reported for the instrument). When the instrument has been repaired or replaced, the On Scan action can be used to set the point back to 'on scan'.
NOTE: The On Scan/Off Scan settings for points are independent of the Field Device's On Scan/Off Scan setting. However, both On Scan/Off Scan settings affect the scanning state for an individual point.
The scanning state of each point is a combination of its individual setting and the Field Device's OnScan/Off Scan setting. If either (or both) is Off Scan, the point is Off Scan. A point is only On Scan if both the Field Device and the point are On Scan.